Network-M2 ファームウェア 3.1.12 リリース

Network-M2のファームウェア 3.1.12 が公開されました。

【重要】ご使用のファームウェアが2.0.5以下(1.x.x含む)の場合、一度2.1.5にアップグレードしてから、3.x.xへアップグレードしてください。2.0.5以下(1.x.x含む)から3.x.xへの直接アップグレードは推奨されていません。

バージョンアップを実施すると、ネットワークカードは再起動しますが、UPS本体は出力を停止することなく稼働し続けます。

以下、Eaton発行のリリースノート(原文)

==========================================================================================
Firmware release notes for Eaton Gigabit Network Card for UPS (Network-M2, P/N 744-A3983)

Firmware : Release 3.1.12
Date     : 2024/01/19
Eaton (c) 2024
==========================================================================================

Upgrade/Compatibility:
    This section describes the considerations for upgrading from a previous release. It is not recommended to upgrade to 3.x.x from 1.x.x directly. 1.x.x firmware versions should first be upgraded to 2.1.5 as an intermediate step and then upgraded to 3.x.x. Note that upgrading to 2.x.x from any 1.x.x firmware revision will clear all alarms and events from the user interface. A backup of these alarms and events is available through RESTful API. See https://www.eaton.com/network-m2 for detailed RESTful API documentation.
	
    Earlier versions can be upgraded to 3.1.8 according to the procedure described in the manual. Downgrade from 1.6.x or above to 1.5.x or below is not possible. Beyond this limitation, downgrade to earlier versions is possible but not recommended.


                              ===============================
                                Release 3.1.12 January 2024
                              ===============================                                                                        
	

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and higher

Supported UPS:		Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130, FERRUPS FX, 9E, 93PM (fw 1.48->), 93PM G2, 93PS (fw 2.50->), 91PS, 93E 15-80 EMEA (fw 8.00.01->), 93E G2 EMEA (fw 4.0.20->)

Supported ATS:      Eaton EATS115, EATS16, EATS120, EATS220

Fixes:

    - Recover communications with Environmental Monitoring Probe in daisy chain configuration after reconnection
    - Corrected sensor alarm messages
    - HID UPS.PowerConverter.Output.Overload[1].Threshold now updating properly
    - Improved data update times
    - Report descriptor timeout changed from 10 sec to 60 sec
    - Cybersecurity updates
    - Various UI improvements
    - Fixed a security vulnerability related to Active Directory

Network-M2 ファームウェアアップグレード手順
https://www.eaton-daitron.jp/techblog/10083.html

ページの先頭へ